Maximum Continuous Operating Pressure SDR11 – 16 bar water (EN 12201-3), 7 bar gas (GIS/PL2) and 10 bar gas (EN 1555-3). Maximum Continuous Operating Pressure SDR17 – 10 bar water (EN 12201-3), 4 bar gas (GIS/PL2) and 5 bar gas (EN 1555-3). Couplers from 400mm upwards are bi filament – have separate fusion zones. Couplers from 355mm upwards have external reinforcement.
* Manual fusion times are based on 39.5 Volt Fusion Boxes. 4.0mm Terminal Pins.
Wolseley code Black | Supplier code Black | Size mm | SDR | Fusion time* (secs) | Cooling time (mins) | Quantity |
---|---|---|---|---|---|---|
P34705 | FL 612 672 | 180 | 11 | 480 | 20 | |
P34706 | FL 612 673 | 200 | 11 | 550 | 20 | |
P34707 | FL 612 674 | 225 | 11 | 550 | 20 | |
P34708 | FL 612 675 | 250 | 11 | 620 | 30 | |
P34737 | FL 615 073 | 280 | 11 | 897 | 30 | |
P34703 | FL 612 670 | 315 | 11 | 1250 | 30 | |
970979 | FL 615 074 | 355 | 11 | 1130 | 30 | |
P34738 | FL 615 075 | 400 | 11 | 750 | 40 | |
P43922 | FL 615 076 | 450 | 11 | Barcode Read | 40 | |
P43923 | FL 615 124 | 500 | 11 | Barcode Read | 40 |